Attempting to restore an unusable HMI
- Unzip and copy all files (provide by us) to a USB disk (FAT-32 formatted)
- Behind HMI, DIP-switch 3 ON (all others OFF)
- Insert the USB-Disk in HMI
- Power on the HMI
- Wait about 1 mn the end (orange message)
- DIP-switch 1 ON (all others OFF)
- Remove USB-Disk
- Restart HMI
- Touch calibration: Press on each red cross
- DIP-switch 2 ON (all others OFF)
- Restart HMI
- With HMI-Tool, upload your project or an empty project
- All DIP-switch OFF