ACE-THL-MB: IP65 Modbus Light, Temperature, Humidity Sensor connected to HMI

 

If you are looking for a light, temperature and humidity sensor to connect to our HMI… Take a look at our ACE-THL-MB

HMI project

 

Basic HMI project for read the sensor values via the Modbus protocole over RS485

Download here
(For ACE-THL-MB Version 1)


HMI screen example

IP65, Slave Modbus RS485
Light + Temperature + Humidity Sensor
Size of the plastic case: 90 x 58 x 35 mm

 

RS485 and power supply wiring

Sensor Wire Colour Sensor Description Sub-D9 HMI RS485
Red / Brown Power + 12-24 VDC  
Green / Black Power – GND  
Yellow RS485 A+ Pin 9
Blue RS485 B- Pin 8

 

RS485 communication parameters

Default 9600 bds, 8 bits, none, 1 stop

 

Registers for reading light/brightness, temperature and humidity data

ACE-THL-MB Version 1 (with Red and Green wires)
Modbus Register
If start from 0
Modbus Register
If start from 1
(*)
Description Data type
4×0 4×1
Luminosity/Light (Lux)
Read only 16 bits unsigned 0 to 65535
4×1 4×2
Temperature (°C *100)
Read only 16 bits signed -4000 to +12300
4×2 4×3
Humidity (% *100)
Read only 16 bits unsigned 0 to 10000
4×102 4×103 Modbus Slave ID / Device address Read / Write 16 bits signed Default 1
4×103 4×104 Baud rate (1=2400,2=4800,3=9600) Read / Write 16 bits signed Default 3 = 9600 bds

 

ACE-THL-MB Version 2 (with Brown and Black wires)
Modbus Register
If start from 0
Modbus Register
If start from 1
(*)
Description Data type
4×0 4×1
Humidity (% *100)
Read only 16 bits unsigned 0 to 65535
4×1 4×2
Temperature (°C *100)
Read only 16 bits signed -4000 to +12300
4×2 4×3
Luminosity/Light (Lux)
Read only 16 bits unsigned 0 to 10000
4×2000 4×2001 Modbus Slave ID / Device address Read / Write 16 bits signed Default 1
4×2001 4×2002 Baud rate (0=2400,1=4800,2=9600) Read / Write 16 bits signed Default 3 = 9600 bds

(*) Addresses always start with 0 for the Modbus RTU protocol, but for technical reasons some controllers start with 1

 

Read with Modbus-Doctor Software

For ACE-THL-MB version 1

  • Modbus-Doctor is connected to a USB to RS485 converter
  • The light, temperature and humidity sensor is supplied with 12 or 24 VDC and connected to terminals A+ and B- of the USB to RS485 converter