How Can We Help?
How do I configure the TB03PWM010-35 3-in/3-out PWM to 0-10V converter?
It is sometimes useful to be able to connect the ACE PLC to a PWM to 0-10 V converter.
For…
- control a frequency inverter via its 0-10 V input.
- convert and scale an analogue value to a 0-10 V value
- control any device with an analogue input
You can have 6 digital inputs, 3 digital outputs and 3 analog outputs with a ACE-11 and a TB03PWM010-35:
This converter is inexpensive for 3 analog outputs, well designed electronically by us and reliable. It has 15 connection terminals. You can buy it here.
ACE digital outputs connector
First, wire the (+) to the 24 VDC (+) to get a 24 VDC on digital output (not 5 VDC by default):
Outputs wiring description
|
|
Wiring of the PWM converter
To ACE PLC (with NPN outputs)
ACE PLC has NPN outputs, not PNP. ACE returns its outputs to 0V when active.
| TB03PWM010-35 | ACE PLC (PLC with NPN Outputs) |
![]() |
|
| PWM 0V | < > | One of its digital output (NPN) | |
| PWM 24V or 12V | < > | + 24 VDC or 12VDC (Same as the ACE PLC) | |
| +24VDC | < > | + 24 VDC (Same as the ACE PLC) | |
| GND | < > | GND – 0VDC (Same as the ACE PLC) |
To any PLC (with PNP outputs)
| TB03PWM010-35 | Others PLC (PLC with PNP outputs) |
![]() |
|
| PWM 0V | < > | GND – 0VDC (Same as the PLC) | |
| PWM 24V or 12V | < > | One of its digital output 12/24V (PNP) | |
| +24VDC | < > | + 24 VDC (Same as the PLC) | |
| GND | < > | GND – 0VDC (Same as the PLC) |
The subroutine for easy integration
Here is the subroutine:
- 3 “OutAna“, the values you want on the PWM 0-10V converter “0-10V OUT” analog outputs
- 3 “OutBitPWM_” : the ACE outputs “OutBit” for the PWM 0-10V converter “PWM IN” inputs

You can import this subroutine (3PWM_To_3ANA.viofs) in your ACE PLC project.

The best value for the PWM signal frequency for this product is 1 kHz. We have set the “Period Length” to 1000 microseconds.

See “PWM – Pulse-width Modulation” page for more information on PWM if you wish to understand this function.
And we scale the values. The converter is lineare, so we need only 2 values for the Scale tool.
For PWM, we use a minimum “On Time” of about 2 microseconds.