How Can We Help?
Communication between a CommandHMI and a Schneider-Crouzet Millenium PLC XN-06 RS485 Module or Zelio Logic Smart Relay PLC SR3-MBU01BD
Wiring from the HMI to the RS485 XN-06 or SR3-MBU01BD module…
XN-06 or SR3-MBU01BD
|
XN-06 Modbus RS485 or SR3-MBU01BD |
||||||||||
|
|
HMI-Tool configuration
Choose
- RS485 (Extended mode) if you have more than 1 Slave device on the network
or - PLC Station if you have only one device on RS485
And select the same communication parameters for HMI and XN-06 (9600,8,NONE,1)
Communication port properties
- Modbus RTU Master
Address entry
- We use 4x and 0x
- Here, 1:4×123 means 1 for Device Slave Number, 4 for Word, 123 for the address in the Modbus register
Adresses Modbus RTU Inputs/Outputs
M3 XN06 |
SR3-MBU01BD |
= 4×16 à 4×31 in the HMI-Tool. |
= 4×16 à 4×23 in the HMI-Tool. |
You can address directly each bit with 4xBit.
Example: The value 32 (100000 in binary) from the HMI (4×17) of the word %MW17 (placed in JXT1) is used to display a fault message (Bit).