Useful HMI reserved and special registers

 

Use your browser’s search [Ctrl] [F] to find the keyword

 

LBxxxxx = BIT

LWxxxxx = WORD

See HMI register types: LB, LW, RWI and retentive/save register

LBxxxxx

Adresse Instruction Notes Read/Write
LB60000-60099 Initial setting ON These bits can be initialized to ON at system startup R/W
LB60100 Recipe download Triggering this bit can write the data in the current RWI to the device, and reset it after completion R/W
LB60101 recipe upload Triggering this bit can read the recipe from the device to the RWI register area, reset after completion R/W
LB60102 Recipe save Triggering this bit can write the recipe from RWI to FLASH, reset after completion R/W
LB60103 Recipe Download Instructions When the recipe is being written to the device, this bit is ON, and it is OFF after downloading R
LB60104 Recipe upload instructions When the recipe is reading the device, this bit is ON, and it is OFF after downloading R
LB60105 Restart the HMI Triggering this bit restarts the system R
LB60106 Backlight Control Control this bit to ON to turn off the LCD backlight, OFF to turn on the LCD backlight R/W
LB60107 COM1 communication status When ON, the communication is normal or there is no communication, and when OFF, the communication fails abnormally. R
LB60108 COM2 communication status When ON, the communication is normal or there is no communication, and when OFF, the communication fails abnormally. R
LB60186 COM3 communication status When ON, the communication is normal or there is no communication, and when OFF, the communication fails abnormally. R
LB60109 COM1 communication parameter modification storage Triggering this bit can write the modified communication parameters into the FLASH storage area, and turns OFF after completion R/W
LB60110 COM2 communication parameter modification storage Triggering this bit can write the modified communication parameters into the FLASH storage area, and turns OFF after completion R/W
LB60187 COM3 communication parameter modification storage Triggering this bit can write the modified communication parameters into the FLASH storage area, and turns OFF after completion R
LB60111 Confirmation and modification of system parameters Triggering this bit can write the modified system parameters into the FLASH storage area, and turns OFF after completion R/W
LB60112 Communication exception window When ON, the exception window is allowed to pop up, and when OFF, the exception window is prohibited from popping up. R/W
LB60113 mouse cursor control When ON, the mouse cursor appears, and when OFF, the cursor is disabled (only when using touch) R/W
LB60114 USB connection status When ON, there is a USB device connected, and when OFF, no USB device is connected. R
LB60115 U-Disk Popup Dialog control When ON, prevent u-disk popup dialog from showing up. R/W
LB60116 touch sound Whether there is a sound when touched or clicked with the mouse R/W
LB60117 alarm sound Is there a sound when an alarm occurs? R/W
LB60118 Clear the historical alarm record The number of historical alarm records is cleared (automatic reset) R/W
LB60119 Operation record clear The number of operation records is cleared (automatic reset) R/W
LB60120 Clear historical data records Historical data record reset (automatic reset) R/W
LB60121 Overload recipe Reload the recipe data of the current recipe serial number, this bit is ON, and it is OFF after reloading R/W
LB60123 Save history alarms When ON, save historical alarm records to flash, and automatically OFF after saving R/W
LB60124 save historical data When ON, save historical data to flash, and automatically OFF after saving R/W
LB60127 Send historical alarm files to U disk Send historical alarm files to U disk, automatically OFF after sending R/W
LB60128 Send historical data files to U disk Send historical data files to U disk, automatically OFF after sending R/W
LB60129 Send current project to U disk Send the project file to the U disk, and automatically turn off after sending R/W
LB60133 The current user is logged in and out When ON, cancels user login and automatically resets after completion R/W
LB60141 There is a realtime alarm happening When a real-time alarm occurs, this bit is ON R
LB60142 The system is in a screen saver state When in the screen saver state, this bit is ON R
LB60143 Copy the operation record to the U disk When ON, send the operation record file to the U disk, and automatically OFF after sending R/W
LB60145 Copy all recipes to U disk When ON, send the recipe file to the U disk, and automatically OFF after sending W
LB60147 USB two-digit barcode scanner scan end mark When ON, triggers R/W
LB60148 Import historical data from U disk trigger bit When ON, trigger; auto reset. The file name of historical data imported by this function must be hisdata+group number.csv, otherwise this function will be invalid. R/W
LB60150 Export the specified ID recipe to the trigger bit of the U disk When ON, trigger; automatically reset R/W
LB60152 Import the specified ID recipe from the U disk to the HMI trigger bit When ON, trigger; automatically reset R/W
LB60154 Clear the specified ID recipe trigger bit When ON, trigger; automatically reset R/W
LB60155 Override Recipe Trigger Bit When ON, trigger; automatically reset R/W
LB60156 Recipe read and save trigger bits When ON, trigger; automatically reset R/W
LB60163 Export recipes to USB stick by group When ON, trigger; automatically reset R/W
LB60165 Ethernet communication identification ON: Normal communication OFF: Communication abnormal R
LB60167 Scan U disk files When ON, trigger; automatic reset, scan the .csv files in the root directory and subdirectories of the U disk, and display them in a pop-up window for import and export of recipe files R/W
LB60168 Export historical data to U disk in groups When ON, trigger; automatically reset, LW60408 sets the export history data group number R/W
LB60169 Station number disable mode selection ON: Automatic mode OFF: Manual mode (default option). Automatic station number disabling and unlocking: When the touch screen uses the extended mode to communicate with multiple devices, a device fails and cannot communicate, the application program automatically disables the station number communication, and there is an automatic reconnection mechanism inside, when the device can communicate normally, automatically unblock, restore communication R/W
LB60173 Restart the VNC server Restart the VNC server R/W
LB60175 Registers control the print window When it is ON, the system automatically resets. The window number to be printed needs to be specified in LW61146. The screen number is invalid R/W
LB60178 TCP communication parameter modification enable flag bit When using the standard mode to connect an Ethernet device, dynamically modify the IP, port number, station number and other parameters of the connected device, and the setting will take effect. For details, please refer to the 63186~63191 address description of [LW]. R/W
LB60179 Dynamic password key modification enable flag Set dynamic password key, set to take effect, automatically reset, key setting address: LW63147 Data type: ASCII Length: 6 R/W
LB60180 Recipe name change trigger bit LW63153 (ASCII input control, length 32), after the formula name is entered, this address will take effect and automatically reset after completion R/W
LB60181 Dynamic password enable flag Set whether the dynamic password function is enabled 0; disable dynamic password 1: enable dynamic password R/W
LB60182 Dynamic password expiration time setting flag Set the dynamic password expiration time, year, month, day, hour: LW63141 ~ 63146 Data type: 16-bit integer, setting the date set after the completion LB60182, set to take effect automatically reset. Note: Password protection process does not allow dynamic updating firmware or dial Code 1.3 to modify the system time, the firmware can be updated after entering the super password R/W
LB60183 Data in the power-off hold area is immediately stored as the trigger bit Q series touch screen by default, the data in the power-off hold area will be automatically stored for 1 minute. By setting this address, the data in the power-off hold area will be stored immediately and automatically reset. R/W

 

LWxxxxx

Adresse Instruction Notes Read/Write
LW44000~44003 Current IP address used In IPs equipment redundancy mode R
LW59010~59025
LW59026~59041
LW59106~59121
LW59042~59057
In extended mode, this register allows communication with a specific station to be enabled or disabled Corresponding station number 0~255, each address corresponds to 16 station numbers, 59010 means station number 0~15, and so on. The X-th bit is 1, allowing the communication with the X station number, and when it is 0, the communication with the X station number is closed. COM1: 59010~59025, COM2: 59026~59041, COM3: 59106~59121, Ethernet: 59042~59057 R/W
LW59058~59073
LW59074~59089
LW59154~59169
LW59090~59105
Station number communication status indication Corresponding to station number 0~255, each address corresponds to 16 station numbers, 59058 means station number 0~15, and so on. The X bit is 1, the station number communication is abnormal; bit is 0, the station number communication is normal. COM1: 59058~59073, COM2: 59074~59089, COM3: 59154~59169, Ethernet: 59090~59105 R
LW60000 local time seconds Bcd code, valid value range 0-59 R/W
LW60001 local time Bcd code, valid value range 0-59 R/W
LW60002 local time Bcd code, valid value range 0-23 R/W
LW60003 local time day Bcd code, valid value range 1-31 R/W
LW60004 local time month Bcd code, valid value range 1-12 R/W
LW60005 local time year Bcd code, valid value range 0-9999 R/W
LW60006 local time week Bcd code, valid value range 1-7 R
LW60007 system runtime The time the system has been running, hours R
LW60008 system running time System elapsed time, minutes R
LW60009 System runtime in seconds System elapsed time, seconds R
LW60010 Current screen window number The serial number of the current screen R
LW60012 current language Corresponding language serial number R
LW60013 Numerical input allowable upper limit value When the custom keyboard pops up, the upper limit of the allowed input is displayed in ASCII R
LW60023 Numerical input allowable lower limit value When the custom keyboard pops up, the lower limit of the allowed input is displayed in ASCII R
LW60033 The input data content displayed on the keyboard The input data content displayed on the keyboard, the characters input from the keyboard, ASCII display R
LW60065 The current system login user current user serial number R
LW60066 Current system login user password Display the current user’s password, 16 characters, ASCII display R
LW60074 The current system login user name Display the current user name, 32 characters, ASCII display R
LW60090 Whether user 1 is enabled 0 – not enabled, 1 – enabled R
LW60091 Whether user 2 is enabled 0 – not enabled, 1 – enabled R
LW60092 Whether user 3 is enabled 0 – not enabled, 1 – enabled R
LW60093 Whether user 4 is enabled 0 – not enabled, 1 – enabled R
LW60094 Whether user 5 is enabled 0 – not enabled, 1 – enabled R
LW60095 Whether user 6 is enabled 0 – not enabled, 1 – enabled R
LW60096 Whether user 7 is enabled 0 – not enabled, 1 – enabled R
LW60097 Whether user 8 is enabled 0 – not enabled, 1 – enabled R
LW60098 User 1 first name 32 characters, ASCII display R
LW60114 User 2 first name 32 characters, ASCII display R
LW60130 User 3 name 32 characters, ASCII display R
LW60146 User 4 first name 32 characters, ASCII display R
LW60162 User 5 name 32 characters, ASCII display R
LW60178 User 6 name 32 characters, ASCII display R
LW60194 User 7 first name 32 characters, ASCII display R
LW60210 User 8 first name 32 characters, ASCII display R
LW60226 User 1 password 16 characters, ASCII display R
LW60234 User 2 password 16 characters, ASCII display R
LW60242 User 3 password 16 characters, ASCII display R
LW60250 User 4 password 16 characters, ASCII display R
LW60258 User 5 password 16 characters, ASCII display R
LW60266 User 6 password 16 characters, ASCII display R
LW60274 User 7 password 16 characters, ASCII display R
LW60282 User 8 password 16 characters, ASCII display R
LW60290 screen saver time Display the screen saver time specified during configuration, the setting range is 0~60 R/W
LW60291 Indicator flashing cycle The blinking period of the indicator light control, the minimum value is 0.1, the unit is s R/W
LW60292 The position of the X when touched The position of the X coordinate when touched R
LW60293 Y’s position when touched The position of the Y coordinate when touched R
LW60294 The position of the X when the touch leaves The position of the X coordinate when the touch leaves R
LW60295 The position of Y when the touch leaves The position of the Y coordinate when the touch leaves R
LW60296 touch state 1-touch, 0-release R
LW60297 Checkout of COM1 Communication parameters, calibration, 0-NONE, 1-EVEN, 2-ODD R/W
LW60298 Baud rate of COM1 Communication parameters, baud rate, 0-1200, 1-2400, 2-4800, 3-9600, 4-19200, 5-38400, 6-57600, 7-115200 R/W
LW60299 stop bit of COM1 Communication parameters, stop bits, 0-1stops, 1-2stops R/W
LW60300 Data length of COM1 Communication parameters, data length, 0-7bits, 1-8bits R/W
LW60301 HMI address of COM1 Communication parameters, HMI address R/W
LW60302 PLC address of COM1 Communication parameters, PLC address R/W
LW60303 COM1 PLC consecutive address interval The length of the maximum continuous address that can be read in a single communication R/W
LW60304 COM1 communication time Communication delay time R/W
LW60305 COM1 retries The number of times the system resends when the communication is abnormal R/W
LW60306 COM1 address mode Address mode, 0-standard mode, 1-extended mode R
LW60307 COM1 communication timeout time Set the communication timeout time, in ms R/W
LW60308 COM1 communication current wait time The current waiting time of communication, in ms R/W
LW60309 COM1 HMI location 0-local, 1-remote R/W
LW60312 Checksum of COM2 Communication parameters, calibration, 0-NONE, 1-EVEN, 2-ODD R/W
LW60313 Baud rate of COM2 Communication parameters, baud rate, 0-1200, 1-2400, 2-4800, 3-9600, 4-19200, 5-38400, 6-57600, 7-115200 R/W
LW60314 stop bit of COM2 Communication parameters, stop bits, 0-1stops, 1-2stops R/W
LW60315 Data length of COM2 Communication parameters, data length, 0-7bits, 1-8bits R/W
LW60316 HMI address of COM2 Communication parameters, HMI address R/W
LW60317 PLC address of COM2 Communication parameters, PLC address R/W
LW60318 COM2 PLC continuous address interval The length of the maximum continuous address that can be read in a single communication R/W
LW60319 COM2 communication time Communication delay time R/W
LW60320 COM2 retries The number of times the system resends when the communication is abnormal R/W
LW60321 COM2 address mode Address mode, 0-standard mode, 1-extended mode R
LW60322 COM2 communication timeout time Set the communication timeout time, in ms R/W
LW60323 COM2 communication current wait time The current waiting time of communication, in ms R/W
LW60324 COM2 HMI location 0-local, 1-remote R/W
LW61216~61247 HMI S/N HMI serial number (S/N) information R
LW61270 Checksum of COM3 Communication parameters, calibration, 0-NONE, 1-EVEN, 2-ODD R/W
LW61271 Baud rate of COM3 Communication parameters, baud rate, 0-1200, 1-2400, 2-4800, 3-9600, 4-19200, 5-38400, 6-57600, 7-115200 R/W
LW61272 stop bit of COM3 Communication parameters, stop bits, 0-1stops, 1-2stops R/W
LW61273 Data length of COM3 Communication parameters, data length, 0-7bits, 1-8bits R/W
LW61274 HMI address of COM3 Communication parameters, HMI address R/W
LW61275 PLC address of COM3 Communication parameters, PLC address R/W
LW61276 COM3 PLC continuous address interval The length of the maximum continuous address that can be read in a single communication R/W
LW61277 COM3 communication time Communication delay time R/W
LW61278 COM3 retries The number of times the system resends when the communication is abnormal R/W
LW61279 COM3 address mode Address mode, 0-standard mode, 1-extended mode R/W
LW61280 COM3 communication timeout time Set the communication timeout time, in ms R/W
LW61281 COM3 communication current wait time The current waiting time of communication, in ms R/W
LW61282 COM3 HMI location 0-local, 1-remote R
LW60327 Number of historical alarms The total number of historical alarms that occurred that were recorded R / double word
LW60329 Number of historical records The total number of historical data records recorded R / double word
LW60333 keyboard language switch 1-Chinese keyboard, 0-English keyboard, for standard keyboard R/W
LW60334 CPU usage CPU runtime usage of the current system R
LW60335 The current brightness value of the backlight The current brightness value of the backlight (140~450) R/W
LW60337 Current project creation time year Current project file creation time year R
LW60338 Current project creation time month Current project file creation time month R
LW60339 Current project creation date and time The current project file creation date and time R
LW60340 current user language set current language W
LW60359 Copy historical alarms by serial number range to U disk When equal to 1, copy the historical alarms of the specified serial number range to the U disk R/W
LW60361 Copy historical alarms by time range to U disk When equal to 1, copy the historical alarms of the specified time range to the U disk R/W
LW60363 Export historical alarm start sequence number R/W
LW60365 Export historical alarm end sequence number R/W
LW60367 Export history alarm start time The length is 6 characters, which are the year, month, day, hour, minute and second. R/W
LW60373 Export historical alarm end time The length is 6 characters, which are the year, month, day, hour, minute and second. R/W
LW60379 File name when exporting historical alarms to U disk 22 characters long R/W
LW60408 The current group number control address of the historical data Specify the current group number of historical data R/W
LW60409 Copy historical data by serial number range to U disk When equal to 1, copy the historical data of the specified serial number range to the U disk R/W
LW60411 Copy historical data by time range to U disk When equal to 1, copy the historical data of the specified time range to the U disk R/W
LW60413 Export historical data start sequence number R/W
LW60415 Export historical data end sequence number R/W
LW60417 Export historical data start time The length is 6 characters, which are the year, month, day, hour, minute and second. R/W
LW60423 End time of exporting historical data The length is 6 characters, which are the year, month, day, hour, minute and second. R/W
LW60429 File name when exporting historical data to U disk 24 characters long R/W
LW60441 Modify User 1 Password Cache 16 characters long, ASCII display R/W
LW60449 Enable to modify the password of user 1 When it is 1, the password of user 1 will be changed to the password of the cache area, and it will be reset automatically after setting. R/W
LW60451 Modify User 2 Password Cache 16 characters long, ASCII display R/W
LW60459 Enable to modify the password of user 2 When it is 1, the password of user 2 will be changed to the password of the cache area, and it will be reset automatically after setting. R/W
LW60461 Modify User 3 Password Cache 16 characters long, ASCII display R/W
LW60469 Enable to modify the password of user 3 When it is 1, the password of user 3 will be changed to the password of the cache area, and it will be reset automatically after setting. R/W
LW60471 Modify User 4 Password Cache 16 characters long, ASCII display R/W
LW60479 Enable to modify the password of user 4 When it is 1, the password of user 4 will be changed to the password of the cache area, and it will be reset automatically after setting. R/W
LW60481 Modify User 5 Password Cache 16 characters long, ASCII display R/W
LW60489 Enable to modify the password of user 5 When it is 1, the password of user 5 will be changed to the password of the cache area, and it will be reset automatically after setting. R/W
LW60491 Modify User 6 Password Cache 16 characters long, ASCII display R/W
LW60499 Enable to modify the password of user 6 When it is 1, the password of user 6 will be changed to the password of the cache area, and it will be reset automatically after setting. R/W
LW60501 Modify user 7 password cache 16 characters long, ASCII display R/W
LW60509 Enable to modify the password of user 7 When it is 1, the password of user 7 will be changed to the password of the cache area, and it will be reset automatically after setting. R/W
LW60511 Modify User 8 Password Cache 16 characters long, ASCII display R/W
LW60519 Enable to modify the password of user 8 When it is 1, the password of user 8 will be changed to the password of the cache area, and it will be reset automatically after setting. R/W
LW60520 HMI model 40 characters R
LW60540 bootloader version number 40 characters R
LW60560 OS version number 40 characters R
LW60580 software version number 40 characters R
LW60600 Operation record enable When it is 1, the operation record is allowed to be recorded R/W
LW60601 Number of operation records Display the number of current operation records R
LW60602 Screen capture enabled When it is 1, enable screen capture and reset automatically after setting R/W
LW60603 Screenshot storage location 0-U disk R/W
LW60604 Enable HMI protection When 1, use HMI protection R/W
LW60605 Set the total number of password levels for HMI protection Set the total number of password levels for HMI protection, up to 15 passwords can be set R/W
LW60606~60835 Setting the lifetime of the HMI protection Blocks of registers store year, month, day, hour, minute, second, expiration prompt screen and unlock password (16 characters) for password levels 1 to 10: 60606-60628 (level 1), 60629-60651 (level 2), 60652-60674 (level 3), 60675-60697 (level 4), 60698-60720 (level 5), 60721-60743 (level 6), 60744-60766 (level 7), 60767-60789 (level 8), 60790-60812 (level 9), 60813-60835 (level 10) R/W
LW63000~63114 Setting the lifetime of the HMI protection (levels 11-15) Blocks of registers store year, month, day, hour, minute, second, expiration prompt screen and unlock password (16 characters) for password levels 11 to 15: 63000-63022 (level 11), 63023-63045 (level 12), 63046-63068 (level 13), 63069-63091 (level 14), 63092-63114 (level 15) R/W
LW63115~63130 The highest level password modification input address The highest level password modification address (password length is 16 characters), after the input is completed, enter 1 in LW63131 to make the currently set password effective R/W
LW63131 Highest level password enable address After the highest level password input (LW63115~63130) is completed, enter 1 in this address to make the highest level password effective R/W
LW60836 Enable store to HMI When it is 1, the HMI protection setting is stored in the HMI, and the setting is automatically reset. R/W
LW60837 Initialize HMI protection state Reset the HMI protection to the initial state. Unlocked users need to unlock again W
LW60997 USB input function assignment Default is 0, USB keyboard input or USB mouse operation. When it is 1, it is used for scanning gun scanning input R/W
LW60998 USB two-digit barcode scanning end symbol definition 0-ENTER, 1-TAB+ENTER R/W
LW60999 USB two-digit barcode scan code length R/W
LW61000~61127 Two-digit barcode scanning code storage and use R/W
LW61128 Use of printer parameters R/W
LW61138 Import recipe source recipe ID number R/W
LW61139 Import recipe destination recipe ID number R/W
LW61140 Clear recipe ID number -1 when the initial value is displayed using a 16-bit integer; otherwise, 65535 R/W
LW61141 Switch the current recipe group number when the HMI is running R/W
LW61143 Specify the group number when importing and exporting the formula U disk R/W
LW61146 Specifies the window number to print when the register triggers printing Enter the serial number of the window to be printed, set LB60175 to trigger printing, and automatically reset R/W
LW62020~62039 Current recipe name ASCII display control, unicode encoding, length 20, displays the current recipe name R
LW62040 User login level selection Set the user level that needs to be logged in, corresponds to the user level checked in “touch screen parameter setting” > “user password setting” option R/W
LW62041~62056 User login password input address Correctly enter LW62040 to set the corresponding password of the user level. The highest authority password can unlock the current user level of all levels (password length is 16 characters), and complete the user login operation. R/W
LW62057 HMI delay times limit register Check the delay option in HMI protection settings, you can modify the number of delays here, the default value is 1 R/W
LW63141~63146 Dynamic Password Expiration Time Settings Year, month, day, hour, minute, second: LW63141~63146, data type 16-bit integer; set LB60182 after setting the date to take effect, resets automatically R/W
LW63147~63152 Dynamic password key setting address Modify the dynamic password key, set address LW63147, data type ASCII length 6; set LB60179 to take effect after setting, resets automatically R/W
LW63153~63184 Formula name modification ASCII input control, length 32; set LB60180 to take effect. After IP, port number and station number setting is completed, set LB60178 to take effect W
LW63186~63189 IP address of the Ethernet device The IP address of the Ethernet device in standard mode, data type 16-bit integer; after setting IP, port number and station number, set LB60178 to take effect R/W
LW63190 Station number of the Ethernet device The station number of the Ethernet device in standard mode, data type 16-bit integer; set LB60178 to take effect after setting R/W
LW63191 Port number of the Ethernet device The port number of the Ethernet device in standard mode, data type 16-bit integer; after setting IP, port number and station number, set LB60178 to take effect R/W
LW60838~60853 Currently logged in user name User rights function, displays the current login user name, control type: ASCII display control, length 32 R
LW63200~63215 Currently logged in user group User rights function, displays the user group name of the currently logged in user (the first group to which he/she belongs), control type: ASCII display control, length 32 R