Useful HMI reserved and special registers
Use your browser’s search [Ctrl] [F] to find the keyword
LBxxxxx = BIT
LWxxxxx = WORD
See HMI register types: LB, LW, RWI and retentive/save register
LBxxxxx |
|||
LB6xxxx | Concerns | Description | Read/Write |
LB60000 LB60099 | Initialization Settings ON | Enable the initialization ON when system starts | R/W |
LB60100 | Download Formula/Recipe | Write the data of this RWI to device if it is triggered; reset after execution | R/W |
LB60101 | Upload Formula/Recipe/Recipe | Read the Formula/Recipe data of device to RWI register if it is triggered; reset after execution | R/W |
LB60102 | Preserve Formula/Recipe | Write Formula/Recipe from RWI to FLASH if it is triggered; reset after execution | R/W |
LB60103 | Formula/Recipe Downloading Indication | ON if Formula/Recipe is being written to device; OFF after the end of downloading | R |
LB60104 | Formula/Recipe Uploading Indication | ON if Formula/Recipe is being read to device; OFF after the end of uploading | R |
LB60105 | Restart HMI | Restart system if it is triggered | R |
LB60106 | Backlight Control | Close Backlight when it is ON; Open Backlight when it is OFF | R/W |
LB60107 | Communication State of COM1 | ON means normal communication; OFF means communication failure or no communication | R |
LB60108 | Communication State of COM2 | ON means normal communication; OFF means communication failure or no communication | R |
LB60109 | Modification preservation of COM1 communication parameters | Write modified communication parameters to FLASH if it is triggered; OFF after execution | R/W |
LB60110 | Modification preservation of COM2 communication parameters | Write modified communication parameters to FLASH if it is triggered; OFF after execution | R/W |
LB60111 | Modification confirmation of system parameters | Write modified communication parameters to FLASH if it is triggered; OFF after execution | R/W |
LB60112 | Abnormal communication window (Comm Error) | ON means permission of exception window popping up; OFF means prohibition | R/W |
LB60113 | Mouse cursor control | ON means disolay of mouse censor; OFF means prohibition (Only available for touch) | R/W |
LB60114 | Connection state of USB | ON means with USB device connection; OFF means no connected USB device | R |
LB60115 | Coonection state of SD card | ON means with SD card connection; OFF means no connected SD card | R |
LB60116 | Touch Sound | Whether enable sound when touch or mouse click | R/W |
LB60117 | Alarm Sound | Whether enable alarm sound when alarm occurs | R/W |
LB60118 | Clear historical alarm record | Clear historical alarm record (Reset automatically) | R/W |
LB60119 | Clear operation record | Clear operation record (Reset automatically) | R/W |
LB60120 | Clear historical data | Clear historical data (Reset automatically) | R/W |
LB60121 | Reload Formula/Recipe | Reload the Formula/Recipe data of the current one while it is ON; OFF when the reloading ends | R/W |
LB60123 | Save historical alarm | Save historical alarm record to disk when it is ON; OFF after the preservation | R/W |
LB60124 | Save historical data | Save historical data to disk when it is ON; OFF after the preservation | R/W |
LB60125 | Send historical alarm file to SD card | Send historical alarm file to SD card; OFF automatically after the sending | R/W |
LB60126 | Send historical data file to SD card | Send historical data file to SD card; OFF automatically after the sending | R/W |
LB60127 | Send historical alarm file to U disk | Send historical alarm file to U disk; OFF automatically after the sending | R/W |
LB60128 | Send historical data file to U disk | Send historical data file to U disk; OFF automatically after the sending | R/W |
LB60129 | Send the current project to U disk | Send the current project to U disk; OFF automatically after the sending | R/W |
LB60130 | Send the current project to SD card | Send the current project to SD card; OFF automatically after the sending | R/W |
LB60133 | User Logout | Cancel User Login when it is ON; Reset automatically after the cancelation | R/W |
LB60141 | Whether there is a real-time alarm | ON when a real-time alarm occurs | R |
LB60142 | Screen saver state of system | ON when it is under screen saver stat | R/W |
LB60143 | Copy operation record to U disk | Send operation record to U disk in case of ON; OFF automatically after the sending | R/W |
LB60144 | Copy operation record to SD card | Send operation record to SD card in case of ON; OFF automatically after the sending | R/W |
LB60145 | Copy all Formula/Recipes to U disk | Send Formula/Recipes to U disk in case of ON; OFF automatically after the sending | W |
LB60146 | Copy Formula/Recipes to SD card | Send Formula/Recipe files to SD card incase of ON; OFF automatically after the sending | W |
LB60147 | End mark of Qrcode scanning USB | Triggered in case of ON | R/W |
LB60148 | Import historical trigger bit from U disk | Triggered in case of ON; reset automatically. Historical data file must be histdata.csv; otherwise the execution is invalid. | R/W |
LB60149 | Import historical trigger bit from SD card | Triggered in case of ON; reset automatically | R/W |
LB60150 | Export specific ID Formula/Recipe to U disk trigger bit | Triggered in case of ON; reset automatically | R/W |
LB60151 | Export specific ID Formula/Recipe to SD card trigger bit | Triggered in case of ON; reset automatically | R/W |
LB60152 | Export specific ID Formula/Recipe from U disk to HMI trigger bit | Triggered in case of ON; reset automatically | R/W |
LB60153 | Export specific ID Formula/Recipe from SD card to HMI trigger bit | Triggered in case of ON; reset automatically | R/W |
LB60154 | Clear trigger bit of specific ID Formula/Recipe trigger bit | Triggered in case of ON; reset automatically | R/W |
LB60155 | Cover Formula/Recipe trigger bit | Triggered in case of ON; reset automatically | R/W |
LB60156 | Read Formula/Recipe and save trigger bit | Triggered in case of ON; reset automatically | R/W |
LB60163 | Export Formula/Recipes to U disk by groups | R/W | |
LB60164 | Export Formula/Recipes to SD card by groups | R/W | |
LB60165 | Ethernet communication | 1=Normal, 0=Error | R |
LB60167 | Usb test function | HMI will scan the touchscreen usb disk for the use of the CVS file for the import and export of the recipe | |
LB60168 | The historical data is exported to USB Disk | Triggered in case of ON; reset automatically | |
LB60169 | Automatic disable function of station number | When using multi-slave “Extended” mode communication, automatically disables or re-enables the faulty station(s) | |
LB60173 | Restart the VNC server | Restart the VNC server | R/W |
LWxxxxx |
|||
LW | Concerns | Description | Read/Write |
LW44000 LW44003 | Current IP address used | Allow to know the current IP address used for the communication to PLC | R |
LW59010 LW59025 | Stop or Run the communication with Slave ID | Each address corresponds to 16 stations/ID slaves on COM1 in RS485 extended mode. | R/W |
LW59026 LW59041 | Stop or Run the communication with Slave ID | Each address corresponds to 16 stations/ID slaves on COM2 in RS485 extended mode. | R/W |
LW59042 LW59057 | Stop or Run the communication with Slave ID | Each address corresponds to 16 stations/ID slaves on ETHERNET in RS485 extended mode. | R/W |
LW59058 LW59073 | Station number communication status COM1 | Corresponding to station number from 0-255, each address corresponds to 16 station numbers. For example, 59058 means station number 0-15, and so on.The X bit is 1 = Communication error with station | R |
LW59074 LW59089 | Station number communication status COM2 | Corresponding to station number from 0-255, each address corresponds to 16 station numbers. For example, 59074 means station number 0-15, and so on.The X bit is 1 = Communication error with station | R |
LW59090 LW59105 | Station number communication status Ethernet | Corresponding to station number from 0-255, each address corresponds to 16 station numbers. For example, 59090 means station number 0-15, and so on.The X bit is 1 = Communication error with station | R |
LW60000 | Local time: second | Bcd code; effective value range: 0-59 | R/W |
LW60001 | Local time: minute | Bcd code; effective value range: 0-59 | R/W |
LW60002 | Local time: hour | Bcd code; effective value range: 0-23 | R/W |
LW60003 | Local time: day | Bcd code; effective value range: 1-31 | R/W |
LW60004 | Local time: month | Bcd code; effective value range: 1-12 | R/W |
LW60005 | Local time: year | Bcd code; effective value range: 0-9999 | R/W |
LW60006 | Local time: week | Bcd code; effective value range: 1-7 | R |
LW60007 | System running hours | Hours of system running time | R |
LW60008 | System running minutes | Minutes of system running time | R |
LW60009 | System running seconds | Seconds of system running time | R |
LW60010 | Serial number of the current screen window | Serial number of the current screen | R |
LW60012 | Current language | Corresponding language serial number | R |
LW60013 | Upper limit of value input | Upper limit of allowable input in user-defined keyboard; ASC display | R |
LW60023 | Lower limit of value input | Lower limit of allowable input in user-defined keyboard; ASC display | R |
LW60033 | Data contents shown in keyboard | Data contents shown in keyboard; characters entered via keyboard; ASC display | R |
LW60065 | Current Logged in User | Current user serial number | R |
LW60066 | Current Logged in User Password | Display the current user password; 16 characters; ASC display | R |
LW60074 | Current logged in User name | Display the current user name; 32 characters; ASC display | R |
LW60090 | Whether enable User 1 | 0-inactivate; 1-activate | R |
LW60091 | Whether enable User 2 | 0-inactivate; 1-activate | R |
LW60092 | Whether enable User 3 | 0-inactivate; 1-activate | R |
LW60093 | Whether enable User 4 | 0-inactivate; 1-activate | R |
LW60094 | Whether enable User 5 | 0-inactivate; 1-activatev | R |
LW60095 | Whether enable User 6 | 0-inactivate; 1-activate | R |
LW60096 | Whether enable User 7 | 0-inactivate; 1-activate | R |
LW60097 | Whether enable User 8 | 0-inactivate; 1-activate | R |
LW60098 | Name of User 1 | 32 characters; ASC display | R |
LW60114 | Name of User 2 | 32 characters; ASC display | R |
LW60130 | Name of User 3 | 32 characters; ASC display | R |
LW60146 | Name of User 4 | 32 characters; ASC display | R |
LW60162 | Name of User 5 | 32 characters; ASC display | R |
LW60178 | Name of User 6 | 32 characters; ASC display | R |
LW60194 | Name of User 7 | 32 characters; ASC display | R |
LW60210 | Name of User 8 | 32 characters; ASC display | R |
LW60226 | Password of User 1 | 16 characters; ASC display | R |
LW60234 | Password of User 2 | 16 characters; ASC display | R |
LW60242 | Password of User 3 | 16 characters; ASC display | R |
LW60250 | Password of User 4 | 16 characters; ASC display | R |
LW60258 | Password of User 5 | 16 characters; ASC display | R |
LW60266 | Password of User 6 | 16 characters; ASC display | R |
LW60274 | Password of User 7 | 16 characters; ASC display | R |
LW60282 | Password of User 8 | 16 characters; ASC display | R |
LW60290 | Screen saver time | Displays the specific screen saver time; setting range: 0-60. Can be used to wake up the HMI screen saver by the PLC: Set it to 0 and then to any value from 0 to 60. | R/W |
LW60291 | Flicker circle of Indicator light | Flicker circle of Indicator light; the minimum value is 0.1s | R/W |
LW60292 | X position in case of touch | Position of X coordinate in case of touch | R |
LW60293 | Y position in case of touch | Position of Y coordinate in case of touch | R |
LW60294 | X position at the end of touch | Position of X coordinate at the end of touch | R |
LW60295 | Y position at the end of touch | Position of Y coordinate at the end of touch | R |
LW60296 | Touch state | 1-Touch; 0-Release | R |
LW60297 | Checking of COM1 | Communication parameters, checking: 0-NONE, 1-EVEN, 2-ODD | R/W |
LW60298 | Baud rate of COM1 | Communication parameters, baud rate: 0-1200,1-2400,2-4800,3-9600,4-19200,5-38400,6-57600,7-115200 | R/W |
LW60299 | Stop Bit of COM1 | Communication parameters, stop bit: 0-1stops,1-2stops | R/W |
LW60300 | Data Length of COM1 | Communication parameters, data length: 0-7bits; 1-8bits | R/W |
LW60301 | HMI Address of COM1 | Communication parameters, HMI address | R/W |
LW60302 | PLC Address of COM1 | Communication parameters, PLC address | R/W |
LW60303 | Continuous address interval of PLC to COM1 | The maximum length of contiguous address that can be read by a single communication | R/W |
LW60304 | Communication time of COM1 | Delay time of communication | R/W |
LW60305 | Retry number of COM1 | Number of retries in case of abnormal system | R/W |
LW60306 | Address Mode of COM1 | Address mode: 0-standard mode; 1-extended mode | R |
LW60307 | Time of COM1 timeout | Set communication timeout; unit: ms | R/W |
LW60308 | Current waiting time of COM1 communication | Current waiting time of communication; unit : ms | R/W |
LW60309 | HMI Site of COM1 | 0-Machine; 1-Far-end | R/W |
LW60312 | Checking of COM2 | Communication parameters, checking: 0-NONE, 1-EVEN, 2-ODD | R/W |
LW60313 | Baud rate of COM2 | Communication parameters, baud rate: 0-1200,1-2400,2-4800,3-9600,4-19200,5-38400,6-57600,7-115200 | R/W |
LW60314 | Stop Bit of COM2 | Communication parameters, stop bit: 0-1stops,1-2stops | R/W |
LW60315 | Data Length of COM2 | Communication parameters, data length: 0-7bits; 1-8bits | R/W |
LW60316 | HMI Address of COM2 | Communication parameters, HMI address | R/W |
LW60317 | PLC Address of COM2 | Communication parameters, PLC address | R/W |
LW60318 | Continuous address interval of PLC to COM2 | The maximum length of contiguous address that can be read by a single communication | R/W |
LW60319 | Communication time of COM2 | Communication delay time | R/W |
LW60320 | Retry number of COM2 | Number of retries in case of abnormal system | R/W |
LW60321 | Address Mode of COM2 | Address mode: 0-standard mode; 1-extended mode | R |
LW60322 | Time of COM2 timeout | Set communication timeout; unit: ms | R/W |
LW60323 | Current waiting time of COM2 communication | Current waiting time of communication; unit : ms | R/W |
LW60324 | HMI Site of COM2 | 0-Machine; 1-Far-end | R/W |
LW60327 | Number of historical alarm | Sum of recorded historical alarm. Double Word | R |
LW60329 | Number of historical data | Sum of recorded historical data. Double Word | R |
LW60333 | Keyboard Language Switch | 1-Chinese keyboard, 0-English keyboard; aim at standard keyboard | R/W |
LW60334 | CPU usage | Current CPU usage rate during the running of system | R |
LW60335 | Backlight luminance value | Backlight luminance value Value from 140 to 450 | R/W |
LW60337 | Creation time of the current project: year | Creation time of the current project: year | R |
LW60338 | Creation time of the current project: month | Creation time of the current project: month | R |
LW60339 | Creation time of the current project: day | Creation time of the current project: day | R |
LW60340 | Current language | Set current language | W |
LW60359 | Copy historical alarm | Copy historical alarm between specific serial number range to U disk when the value is 1 | R/W |
LW60360 | Copy historical alarm | Copy historical alarm between specific serial number range to SD card when the value is 1 | R/W |
LW60361 | Copy historical alarm | Copy historical alarm between specific time range to U disk when the value is 1 | R/W |
LW60362 | Copy historical alarm | Copy historical alarm between specific time range to SD card when the value is 1 | R/W |
LW60363 | Export the start serial number of historical alarm | Export the start serial number of historical alarm | R/W |
LW60365 | Export the end serial number of historical alarm | Export the end serial number of historical alarm | R/W |
LW60367 | Export start time of historical alarm | Length: six characters; year, month, day, hour, minute and second | R/W |
LW60373 | Export end time of historical alarm | Length: six characters; year, month, day, hour, minute and second | R/W |
LW60379 | File name of historical alarm exported to U disk and SD card | Length: 24 characters | R/W |
LW60408 | Historical data | Current group number of historical data imported or exported | R/W |
LW60409 | Historical data | Copy historical data between specific serial number range to U disk when the value is 1 | R/W |
LW60410 | Historical data | Copy historical data between specific serial number range to SD card when the value is 1 | R/W |
LW60411 | Historical data | Copy historical data between specific time range to U disk when the value is 1 | R/W |
LW60412 | Historical data | Copy historical data between specific time range to SD card when the value is 1 | R/W |
LW60413 | Export start serial number of historical data | R/W | |
LW60415 | Export end serial number of historical data | R/W | |
LW60417 | Export start time of historical data | Length: six characters; year, month, day, hour, minute and second | R/W |
LW60423 | Export end time of historical data | Length: six characters; year, month, day, hour, minute and second | R/W |
LW60429 | File name of historical data exported to U disk and SD card | Length: 24 characters | R/W |
LW60441 | Cache region of password modification of User 1 | Length: 16 characters; ASC display | R/W |
LW60449 | Enable modify password of User 1 | Modify the password of User 1 as that in cache region when the value is 1; reset automatically after setting | R/W |
LW60451 | Cache region of password modification of User 2 | Length: 16 characters; ASC display | R/W |
LW60459 | Enable modify password of User 2 | Modify the password of User 2 as that in cache region when the value is 1; reset automatically after setting | R/W |
LW60461 | Cache region of password modification of User 3 | Length: 16 characters; ASC display | R/W |
LW60469 | Enable modify password of User 3 | Modify the password of User 3 as that in cache region when the value is 1; reset automatically after setting | R/W |
LW60471 | Cache region of password modification of User 4 | Length: 16 characters; ASC display | R/W |
LW60479 | Enable modify password of User 4 | Modify the password of User 4 as that in cache region when the value is 1; reset automatically after setting | R/W |
LW60481 | Cache region of password modification of User 5 | Length: 16 characters; ASC display | R/W |
LW60489 | Enable modify password of User 5 | Modify the password of User 5 as that in cache region when the value is 1; reset automatically after setting | R/W |
LW60491 | Cache region of password modification of User 6 | Length: 16 characters; ASC display | R/W |
LW60499 | Enable modify password of User 6 | Modify the password of User 6 as that in cache region when the value is 1; reset automatically after setting | R/W |
LW60501 | Cache region of password modification of User 7 | Length: 16 characters; ASC display | R/W |
LW60509 | Enable modify password of User 7 | Modify the password of User 7 as that in cache region when the value is 1; reset automatically after setting | R/W |
LW60511 | Cache region of password modification of User 8 | Length: 16 characters; ASC display | R/W |
LW60519 | Enable modify password of User 8 | Modify the password of User 8 as that in cache region when the value is 1; reset automatically after setting | R/W |
LW60520 | HMI Model | 40 characters | R |
LW60540 | Bootloader version number | 40 characters | R |
LW60560 | Operation system version number | 40 characters | R |
LW60580 | Software version number | 40 characters | R |
LW60600 | Enable operation record | Enable record operation log when it is 1 | R/W |
LW60601 | Number of operation record | Display the current number of operation record | R |
LW60602 | Enable screen shot | Enable screen shot when it is 1; reset after setting | R/W |
LW60603 | Storage location of screen shot | 0-U disk; 1-SD card | R/W |
LW60604 | Enable HMI protection | Enable HMI protection when it is 1 | R/W |
LW60605 | Set the level number of HMI protection password | Set the level number of HMI protection password; up to 10 passwords can be set | R/W |
LW60606 – LW60835 | Set period of validity of HMI protection | is for year, month, day, hour, minute, second, deadline prompt and unlock password protection of Level 1 password (password length is 16 characters); | R/W |
LW60629 -LW60651 | Set period of validity of HMI protection | is for year, month, day, hour, minute, second, deadline prompt and unlock password protection of Level 2 password (password length is 16 characters); | R/W |
LW60652 -LW60674 | Set period of validity of HMI protection | is for year, month, day, hour, minute, second, deadline prompt and unlock password protection of Level 3 password (password length is 16 characters); | R/W |
LW60675 -LW60697 | Set period of validity of HMI protection | is for year, month, day, hour, minute, second, deadline prompt and unlock password protection of Level 4 password (password length is 16 characters); | R/W |
LW60698 -LW60720 | Set period of validity of HMI protection | is for year, month, day, hour, minute, second, deadline prompt and unlock password protection of Level 5 password (password length is 16 characters); | R/W |
LW60721 -LW60743 | Set period of validity of HMI protection | is for year, month, day, hour, minute, second, deadline prompt and unlock password protection of Level 6 password (password length is 16 characters); | R/W |
LW60744 -LW60766 | Set period of validity of HMI protection | is for year, month, day, hour, minute, second, deadline prompt and unlock password protection of Level 7 password (password length is 16 characters); | R/W |
LW60767 -LW60789 | Set period of validity of HMI protection | is for year, month, day, hour, minute, second, deadline prompt and unlock password protection of Level 8 password (password length is 16 characters); | R/W |
LW60790 -LW60812 | Set period of validity of HMI protection | is for year, month, day, hour, minute, second, deadline prompt and unlock password protection of Level 9 password (password length is 16 characters); | R/W |
LW60813 -LW60835 | Set period of validity of HMI protection | is for year, month, day, hour, minute, second, deadline prompt and unlock password protection of Level 10 password (password length is 16 characters) | R/W |
LW60836 | Enable save to HMI | Preserve the HMI protection settings to HMI when it is 1; reset automatically after setting | R/W |
LW60837 | Initialize HMI protection | Set HMI protection to the initial state | W |
LW60997 | Keyboard input or USB mouse operation | Scanning machine input when the value is 1. Triggered when it is ON; reset automatically | R/W |
LW60998 | End Symbol definition of USB bar code scanning | End Symbol definition of USB bar code scanning. 0-ENTER,1-TAB+ENTER | R/W |
LW60999 | Scan code length of USB bar code | Scan code length of USB bar code | R/W |
LW61000 -LW61127 | Storage usage of bar code scanning | Storage usage of bar code scanning | R/W |
LW61128 | Employed for printer parameters | Employed for printer parameters | R/W |
LW61138 | Source Formula/Recipe ID number of imported Formula/Recipe | Source Formula/Recipe ID number of imported Formula/Recipe | R/W |
LW61139 | Target Formula/Recipe ID number of imported Formula/Recipe | Target Formula/Recipe ID number of imported Formula/Recipe | R/W |
LW61140 | Clear Formula/Recipe ID number | -1 when initial value is presented as a 16-Bit integer; otherwise, 65535 | R/W |
LW61141 | Switch Formula/Recipe group number | R/W | |
LW61143 | Specific Formula/Recipe group number | R/W | |
LW61216 LW61247 | HMI serial number (S/N) information | ASCII character display 32 lenght | R |
LW62020 – LW62039 | Current Formula/Recipe name | Displays the current formula/recipe name. Select “ASCII Display” control, check “Use Unicode”, length 20. | R |